Conduit Fill Calculator

Six 12 AWG wires and two 10 AWG wires in 3/4 inch EMT fill 22.9% of the conduit, under the 40% limit for three or more wires. Choose EMT, PVC Schedule 40 or PVC Schedule 80, a trade size from 1/2 to 4 inch and up to three groups of copper THHN/THWN-2 wires to see the fill, the limit, a pass or fail and the most same-size wires that fit. It is a planning check only.

Enter your conduit and wires

The trade size is a name, not the inside width. The calculator uses the NEC internal area for it.

A whole number. Use rows 2 and 3 for other sizes, and 0 for a row you do not need.

A whole number, or 0 if you do not need this row.

A whole number, or 0 if you do not need this row.

Conduit fill

22.9% of the conduit

Within the limit · limit 40% for 8 wires · 3/4 inch EMT (electrical metallic tubing)

Your conduit and the limit
Conduit3/4 inch EMT (electrical metallic tubing)
Internal area of the conduit0.533 sq in
Total wire area0.1220 sq in (8 wires)
Fill22.89%
Limit for 8 wires40% = 0.2132 sq in of wire
Room left under the limit0.0912 sq in
ResultPasses the fill limit
Your wires (THHN/THWN-2 copper)
WireHow manyArea of one wireArea of all
12 AWG60.0133 sq in0.0798 sq in
10 AWG20.0211 sq in0.0422 sq in
Most same-size wires in 3/4 inch EMT (electrical metallic tubing)
WireArea of one wireMost wires of that size
14 AWG0.0097 sq in22
12 AWG0.0133 sq in16
10 AWG0.0211 sq in10
8 AWG0.0366 sq in6
6 AWG0.0507 sq in4
4 AWG0.0824 sq in2
3 AWG0.0973 sq in1
2 AWG0.1158 sq in1
The same wires in 3/4 inch conduit of each type
ConduitInternal areaFillResult
EMT (electrical metallic tubing)0.533 sq in22.9%Passes
PVC Schedule 400.508 sq in24.0%Passes
PVC Schedule 800.409 sq in29.8%Passes

Formulas: fill % = total wire area ÷ conduit internal area × 100; the limit is 53% for one wire, 31% for two wires and 40% for three or more wires (NEC Chapter 9, Table 1). Conduit areas come from Table 4 and wire areas from Table 5. The most same-size wires is the allowed area divided by the area of one wire, rounded down, except that a fraction of .8 or more is rounded up when every wire is the same size, as an NEC note allows; mixed sizes are not rounded up. The limits are for conduit longer than 24 inches; Table 4 also lists a 60% column for shorter sections, which this calculator does not use. Count every wire you pull, including any ground wire, as its own wire. Only copper THHN/THWN-2 in sizes 14 to 2 AWG is included, and bends, pull length and cable types are not checked.

Planning check only. Your local electrical code and a licensed electrician have the last word.

How do I calculate conduit fill?

Add up the cross-section area of every wire, divide by the internal area of the conduit, and compare the percentage with the limit. For the example below, 0.1220 square inches of wire in a conduit with 0.533 square inches inside is 22.9% fill.

Fill % = total wire area ÷ conduit internal area × 100
Total wire area = (number of wires × area of one wire), added for each wire size
Pass when fill % is at or below the limit for the number of wires

Example: 6 wires of 12 AWG and 2 wires of 10 AWG in 3/4 inch EMT
ItemValue
6 wires of 12 AWG0.0798 sq in
2 wires of 10 AWG0.0422 sq in
Total wire area0.1220 sq in
Internal area of 3/4 inch EMT0.533 sq in
Fill22.9%
Limit for 8 wires40% = 0.2132 sq in
ResultPasses

Wire areas come from Table 5 of NEC Chapter 9 and conduit areas from Table 4. The two are compared as whole numbers, so a fill exactly on the limit is not lost to rounding.

What are the fill limits for one, two and three or more wires?

Table 1 of NEC Chapter 9 allows 53% of the conduit for one wire, 31% for two wires and 40% for three or more wires. The count is the total number of wires, so the limit changes as you add a row.

Two wires have the tighter limit. In 1/2 inch EMT, one 6 AWG wire fills 16.7% and passes the 53% limit, while two 6 AWG wires fill 33.4% and fail the 31% limit. The table shows how many wires of one size fit.

Most same-size wires in EMT, by trade size
Trade size14 AWG12 AWG10 AWG8 AWG6 AWG
1/2 inch129531
3/4 inch22161064
1 inch35261697
1-1/4 inch6145281612
1-1/2 inch8461382216
2 inch138101633626

Each figure is the 40% area divided by the area of one wire, rounded down, except that a fraction of .8 or more is rounded up when every wire is the same size, as an NEC note allows. Mixed sizes are not rounded up. For two wires the 31% limit applies instead, which can cut the count to 1: 6 AWG in 1/2 inch EMT gives 2.4 by the 40% rule, but two wires fill 33.4%, above 31%, so the table shows 1.

How does PVC compare with EMT?

At every trade size in Table 4, Schedule 80 PVC has less internal area than Schedule 40, and both differ from EMT. The same wires from the example fill 22.9% of 3/4 inch EMT, 24.0% of 3/4 inch Schedule 40 and 29.8% of 3/4 inch Schedule 80.

Most 12 AWG wires by conduit type
Trade sizeEMTPVC Schedule 40PVC Schedule 80
1/2 inch986
3/4 inch161512
1 inch262520
1-1/4 inch454337
1-1/2 inch615951
2 inch1019986

What should I check before I pull the wire?

Fill is only one check. Wire size starts from the load: the watts to amps calculator turns watts into amps, and the guide How many watts on a 15 amp circuit shows what a common circuit carries. For a long run, the voltage drop calculator shows whether the wire is large enough over the distance.

Count every wire you will pull, including a ground wire. The limits here are for conduit longer than 24 inches and copper THHN/THWN-2 in sizes 14 to 2 AWG. Bends, pulling tension, other wire types and the amps a wire may carry are not checked.

This is a planning check only. Your local electrical code and a licensed electrician have the last word.

Sources

  • NFPA 70, National Electrical Code, Chapter 9, Table 1 (percent of cross section of conduit and tubing for conductors: 53% for one wire, 31% for two wires, 40% for over two wires), Table 4 (dimensions and percent area of conduit and tubing: EMT, rigid PVC Schedule 40 and Schedule 80) and Table 5 (dimensions of insulated conductors: THHN, THWN, THWN-2).
  • Table 4 and Table 5 values as read on the NECA-IBEW Electricians site (necaibewelectricians.com), the International Code Council sample page "Area of Conductor Types" and the Steel Tube Institute page "NEC Conduit and EMT Fill Tables".

Check the code edition your area has adopted before you rely on a result.

Conduit Fill Calculator FAQ

How many 12 AWG wires fit in 1/2 inch EMT?

Up to 9 THHN/THWN-2 wires of 12 AWG fit under the 40% limit for three or more wires. In 1/2 inch Schedule 40 PVC the figure is 8, and in Schedule 80 it is 6.

What is the maximum conduit fill for three or more wires?

The limit is 40% of the internal area of the conduit for three or more wires, from Table 1 of NEC Chapter 9. Three 12 AWG wires in 1/2 inch EMT fill 13.1%, so they pass with room to spare.

What is the fill limit for one wire or two wires?

One wire may fill 53% of the conduit and two wires 31%. Two 6 AWG wires in 1/2 inch EMT fill 33.4%, over the 31% limit, even though one 6 AWG wire passes.

Is PVC Schedule 80 smaller inside than Schedule 40?

Yes. Schedule 80 has less internal area at every trade size; for 3/4 inch conduit it is 0.409 square inches against 0.508 for Schedule 40, and fewer wires fit.

Can I use a conduit fill result for a permit or an inspection?

No, treat it as a planning check. The local electrical code, the edition your area has adopted and a licensed electrician decide what is allowed for your job.