How voltage drop is calculated
Every wire has a small resistance, and a current flowing through resistance loses voltage along the way. The current travels out to the load and back again, so the resistance that counts is that of twice the one-way length on a single-phase or direct-current circuit. For three-phase, the loop factor is the square root of 3, about 1.732, instead of 2.
Resistance of the run = factor × one-way length × ohms per 1,000 ft ÷ 1,000
Voltage drop = resistance of the run × current
Percent drop = voltage drop ÷ source voltage × 100
Voltage at the load = source voltage − voltage drop
The calculator takes ohms per 1,000 feet from the direct-current resistance of stranded, uncoated copper and aluminum at 75 °C (167 °F) in Chapter 9, Table 8 of the National Electrical Code.
Worked example: 50 feet of 12 AWG copper at 16 amps
A 120-volt source feeds a load that draws 16 amps through 50 feet of 12 AWG copper wire. Table 8 lists 1.98 ohms per 1,000 feet for this size.
- Resistance of the run: 2 × 50 × 1.98 ÷ 1,000 = 0.198 ohms
- Voltage drop: 0.198 × 16 = 3.168 V, which rounds to 3.17 V
- Percent drop: 3.168 ÷ 120 × 100 = 2.64%
- Voltage at the load: 120 − 3.168 = 116.83 V
Moving up to 10 AWG copper lowers the drop to 1.98 V, or 1.65%. The same run in 12 AWG aluminum drops 5.2 V (4.33%), because Table 8 gives it 3.25 ohms per 1,000 feet against 1.98 for copper. A three-phase circuit at 208 V drops 2.74 V, or 1.32%.
How far can you run each wire size?
Doubling the length doubles the drop, and so does doubling the current. Turned around, that gives the longest run that stays at 3% or less. The table runs the calculator at each size and current on a 120-volt circuit.
| Wire size | 10 amps | 15 amps | 20 amps | 30 amps |
|---|---|---|---|---|
| 14 AWG | 57 ft | 38 ft | 28 ft | 19 ft |
| 12 AWG | 90 ft | 60 ft | 45 ft | 30 ft |
| 10 AWG | 145 ft | 96 ft | 72 ft | 48 ft |
| 8 AWG | 231 ft | 154 ft | 115 ft | 77 ft |
| 6 AWG | 366 ft | 244 ft | 183 ft | 122 ft |
| 4 AWG | 584 ft | 389 ft | 292 ft | 194 ft |
It shows voltage drop only. The wire must also be rated for the current, which is a separate NEC ampacity check.
Example: a 20-amp load sits 100 feet from the panel. 12 AWG drops 7.92 V (6.6%) and 10 AWG drops 4.96 V (4.13%). 8 AWG drops 3.11 V, or 2.59%, the smallest size here within 3%.
What drop is acceptable
EC&M (2015) reports that the NEC gives a recommendation, in an informational note, of 3% for any branch circuit and 5% for the combined drop of feeder and branch-circuit conductors. EC&M states that these are recommendations and not NEC requirements. Its article also notes that the NEC ampacity tables do not take voltage drop into consideration, so a wire can be large enough for the current and still lose too much voltage over a long run. The default example loses 2.64%. For comparison, the figure that EC&M reports as the NEC's recommendation for a branch circuit is 3%.
Low-voltage and 240-volt circuits
The same volts lost weigh far more at low voltage. A 12-volt, 10-amp load 20 feet away on 10 AWG copper loses 0.5 V, which is 4.13% of 12 V and leaves 11.5 V. The single-phase option covers battery and solar wiring.
At 240 volts it is the reverse. The same 16-amp, 50-foot, 12 AWG run on a 240-volt source still loses 3.17 V, but that is only 1.32% of the source: doubling the voltage halves the percent for the same wire, length and current.
Limits of this estimate
The tool does not check the wire's ampacity, the breaker or fuse, the installation or the temperature. Those choices must follow the NEC as adopted where you live and the advice of a licensed electrician. The tool ignores reactance and skin effect, so on AC circuits with large conductors or a low power factor the real drop can be higher.
To convert watts to amps first, use the watts to amps calculator. The watts, amps and volts guide explains the terms, and how many watts a 15-amp circuit carries shows a typical load. The generator size and solar panel calculators size the source, and the electricity cost calculator prices what a device uses.
Voltage Drop Calculator FAQ
How do I calculate voltage drop in a wire?
Multiply the one-way length by 2 (or by 1.732 for three-phase), by the ohms per 1,000 feet, divided by 1,000, and by the current. For 50 feet of 12 AWG copper at 16 amps that is 3.17 volts.
How far can I run 12 gauge wire on a 20-amp circuit?
For a 3% drop at 120 volts, about 45 feet one way in copper. At 15 amps it is 60 feet. The wire must also be rated for the current.
What size wire do I need for 100 feet at 20 amps?
For a drop of 3% or less at 120 volts, 8 AWG copper: it drops 2.59%, against 4.13% for 10 AWG and 6.6% for 12 AWG. Check ampacity and local rules too.
Does the NEC set a limit on voltage drop?
According to EC&M, the NEC only recommends 3% on a branch circuit and 5% for feeder and branch circuit together, in informational notes, and these are not requirements.
Can I use this for a DC circuit such as solar or a battery?
Yes, the single-phase option uses the same loop of two conductors, with the direct-current resistance. Enter the battery or panel voltage as the source voltage.