GuideElectrical & Energy

Watts vs Amps vs Volts: What Is the Difference?

Volts push, amps flow and watts do the work. Learn how the three connect, what one amp means in watts at 120 and 240 volts, and why the voltage decides the current.

Updated 7 min read

Short answer

Volts are the electrical pressure, amps are the flow of current, and watts are the power that results: watts = volts × amps. A 1,500-watt heater on a 120-volt outlet draws 12.5 amps. The same 1,500 watts on a 240-volt supply draws 6.25 amps. You need the voltage to turn watts into amps.

Do the math for your project

Watts to Amps Calculator

Convert watts to amps and amps to watts, or solve Ohm's law for volts, amps, ohms and watts.

Open the Watts to Amps Calculator

What is the difference between watts, amps and volts?

The U.S. Energy Information Administration (EIA) explains the three with a hose. Voltage is the pressure applied to electrons to make them move, and it is the electrical counterpart of water pressure. Current is the flow, measured in amperes, or amps. Electrical power, measured in watts, combines the two: the water pressure and the rate of flow.

Volts, amps and watts side by side
UnitWhat it measuresSymbolWater in a hoseSI definition (NIST)
VoltElectrical pressure that pushes currentVWater pressure1 watt per ampere
AmpHow much current flowsARate of flowSI base unit
WattPower: the rate energy is usedWPressure and flow together1 joule per second

The National Institute of Standards and Technology (NIST) lists the same relationships in the SI. The ampere is a base unit, the watt is a joule per second, and the volt is a watt per ampere. That last line is the whole idea in one phrase: one volt is one watt for each amp of current.

Watts = volts × amps
Amps = watts ÷ volts
Volts = watts ÷ amps

The Electrical Safety Foundation International (ESFI) prints the first line in its home safety booklet as volts × amps = watts. The three lines are one equation solved three ways.

How do watts, amps and volts work together?

Take a 1,500-watt device. At 120 volts the current is 1,500 ÷ 120 = 12.5 amps. At 240 volts the current is 1,500 ÷ 240 = 6.25 amps. The device does the same work in both cases. Only the split between pressure and flow changes.

Turn it around to check: 12.5 A × 120 V = 1,500 W, and 6.25 A × 240 V = 1,500 W. The watts to amps calculator shows the same numbers, and its Ohm's law mode adds resistance when you know two of the four values.

The formula as written assumes a power factor of 1, which fits a resistive load such as a heater. Below a power factor of 1, the same watts need more current. At a power factor of 0.8, the same 1,500 watts at 120 volts needs 15.63 amps, not 12.5. The label or data sheet gives the power factor when it matters.

Tip: If a label shows only volts and amps, multiply them for volt-amps. For a resistive load such as a heater, that equals the watts.

Open 1,500 watts at 120 volts in the watts to amps calculator

How many watts is one amp?

It depends on the voltage, because one amp carries as many watts as the volts behind it. One amp is 120 watts on a 120-volt circuit and 240 watts on a 240-volt circuit. There is no single answer without the voltage.

What a current in amps means in watts (single-phase, power factor 1)
CurrentWatts at 120 VWatts at 240 V
1 A120 W240 W
5 A600 W1,200 W
10 A1,200 W2,400 W
12 A1,440 W2,880 W
15 A1,800 W3,600 W
16 A1,920 W3,840 W
20 A2,400 W4,800 W
30 A3,600 W7,200 W

The 12 and 16 amp rows are the 80% limits of a 15-amp and a 20-amp breaker. The watts a circuit should carry are lower than the full ratings, and the guide how many watts can a 15-amp circuit handle explains the 80% limit step by step.

Which household appliances use 120 volts and which use 240?

Virginia Cooperative Extension says most appliances in the United States use 120 volts, and larger appliances, such as clothes dryers and electric cook tops, use 240 volts. Its guide also tells you to read the wattage on the appliance itself, stamped on the bottom or back or on the nameplate.

The table takes the wattage ranges from that guide and shows the amps at the voltage each one uses. The amps are our arithmetic, computed with the same formula as the calculator. Real wattage varies by model and setting.

Typical appliance watts (Virginia Cooperative Extension) turned into amps
ApplianceWattsVolts usedAmps drawn
Laptop501200.42
Ceiling fan65 to 1751200.54 to 1.46
Microwave oven750 to 1,1001206.25 to 9.17
Toaster800 to 1,4001206.67 to 11.67
Coffee maker900 to 1,2001207.5 to 10
Portable heater750 to 1,5001206.25 to 12.5
Hair dryer1,200 to 1,87512010 to 15.63
Clothes dryer1,800 to 5,0002407.5 to 20.83

The dryer row uses the 240 volts the guide gives for dryers. Even at 5,000 watts the current is 20.83 amps, because the voltage is doubled. At 120 volts the same 5,000 watts would need 41.7 amps, far above the 15 and 20 amp breaker ratings discussed in the 15-amp circuit guide. The generator size calculator uses the same idea to add up running watts.

Why does 240 volts use half the amps?

For a fixed number of watts, doubling the volts halves the amps. That matters because a wire loses energy as heat in proportion to the square of the current: power lost = amps × amps × resistance. Half the current means a quarter of the heat in the same wire.

Here is a worked example with numbers from the voltage drop calculator. A 1,440-watt load sits at the end of 100 feet of 12 AWG copper wire, measured one way. The calculator uses 1.98 ohms per 1,000 feet for 12 AWG copper, the direct-current resistance at 75 °C from NEC Chapter 9, Table 8, as its own page states. The loop is twice the length, so 0.396 ohms in total.

The same 1,440 watts through 100 feet of 12 AWG copper wire (one way)
SupplyCurrentVolts lostPercent lostHeat in the wire
120 V12 A4.75 V3.96%57 W
240 V6 A2.38 V0.99%14.3 W

At 120 volts the load pulls 12 amps and the wire drops 4.75 volts, which is 3.96% of the supply. At 240 volts it pulls 6 amps, and the drop is 2.38 volts, 0.99% of the supply. The wire wastes 57 watts in the first case and 14.3 watts in the second. This is a planning illustration of the physics, not a wire size recommendation.

How do I read volts, amps and watts on a label?

Most appliance labels give watts, or volts and amps, or both. Use whichever pair you have to find the third with the formula, or enter it in the watts to amps calculator. If the watts are missing, Virginia Cooperative Extension says to find the current draw in amps and multiply it by the voltage.

  • Watts and volts given: amps = watts ÷ volts.
  • Amps and volts given: watts = amps × volts, as the label rating and not a measured value.

Three mix-ups cause most mistakes. A watt is a rate of power, while a watt-hour or kilowatt-hour is energy over time, explained in what is a kilowatt-hour. An amp is a current, while an amp-hour is a battery capacity, covered by the battery runtime calculator. And a breaker's amp rating is a limit on the circuit, not what a device draws.

When should I ask an electrician?

The math on this page tells you what a load draws. It does not tell you what wire, breaker or outlet a circuit needs, and it does not replace the National Electrical Code (NEC) as adopted where you live. A licensed electrician should make any change to wiring, breakers or outlets, and any 240-volt work. To price what a device costs to run, use the electricity cost calculator.

Frequently asked questions

Do more volts mean more watts?

Only if the amps stay the same. Watts = volts × amps, so 10 amps at 120 volts is 1,200 watts and 10 amps at 240 volts is 2,400 watts. A device is rated at the voltage on its label, so follow the label and do not use voltage to get more power.

How many watts is 1 amp?

One amp is 120 watts at 120 volts and 240 watts at 240 volts, with a power factor of 1. The answer always depends on the voltage.

Why do dryers and cook tops use 240 volts?

Virginia Cooperative Extension says larger appliances such as clothes dryers and electric cook tops use 240 volts. For the same watts, 240 volts needs half the amps, which means less heat in the wire, as the 1,440-watt example on this page shows.

What does the power factor change?

It changes the amps, not the watts. At a power factor of 1, 1,500 watts at 120 volts draws 12.5 amps. At 0.8 the same watts draw 15.63 amps.

Do watts and amps add up on one circuit?

Yes, on the same voltage. Add the watts of every device on the circuit, or add their amps, and divide or multiply by the same voltage. Two 600-watt devices on 120 volts total 1,200 watts, which is 10 amps.

Sources

  1. EIA: Measuring Electricity, intermediate and secondary lesson plan (volts, amps, watts and the water analogy)eia.gov
  2. NIST: Guide to the SI, Chapter 4, Table 3 (watt, volt and the ampere as a base unit)nist.gov
  3. Virginia Cooperative Extension: Estimating Appliance and Home Electronic Energy Use (2901-9014, February 26, 2020)pubs.ext.vt.edu
  4. ESFI: Indoor Electrical Safety Check booklet (volts × amps = watts)esfi.org