Water Heater Size Calculator

What size water heater do you need? For a tankless model, enter the showers and faucets you run at the same time and the water temperatures: the calculator gives the flow rate and the temperature rise to look for. For a storage tank, count the hot water uses in your busiest hour to get the first hour rating to look for. Both methods come from the U.S. Department of Energy.

Enter your hot water use

Whole number, 0 for none.

On the shower head, or time a bucket for one minute.

Whole number, 0 for none.

The DOE example uses 0.75 gpm.

Optional, for example a tub or a washer filling. 0 for none.

DOE: assume 50 °F (10 °C) unless you know otherwise.

DOE: 120 °F (49 °C) for most uses.

Look for a tankless unit that gives

3.25 gpm

at a temperature rise of 70 °F · 12.3 L per minute

Flow rate and temperature rise
Showers at once1 × 2.5 gpm = 2.5 gpm
Faucets at once1 × 0.75 gpm = 0.75 gpm
Other flow at once0 gpm
Flow rate needed3.25 gpm (12.3 L/min)
Incoming water50 °F
Hot water wanted120 °F
Temperature rise needed70 °F (38.9 °C)

Method (U.S. Department of Energy): flow rate = the flow rates of the fixtures you expect to run at the same time, added together; temperature rise = hot water temperature − incoming water temperature. A tankless model is rated by the temperature rise it can give at a given flow rate, so compare both numbers with the maker's chart.

Sizing a tankless water heater

The Energy Saver guide of the U.S. Department of Energy (DOE) explains that tankless, or demand, water heaters are rated by the maximum temperature rise they can give at a given flow rate. So you need two numbers: the flow of hot water you use at the same time, and how much the water has to be heated.

Flow rate (gpm) = sum of the flow rates of the fixtures used at the same time
Temperature rise = hot water temperature − incoming water temperature

Count only what really runs together, such as a shower and a kitchen faucet in the morning. If you do not know a flow rate, DOE suggests timing how much water fills a pan or a bucket in one minute. Low-flow fixtures reduce the flow rate you need.

Incoming and hot water temperatures

DOE says to assume an incoming water temperature of 50 °F (10 °C) unless you know otherwise. For most uses it gives a hot water temperature of 120 °F (49 °C), which makes a rise of 70 °F. A dishwasher without its own heater may need 140 °F (60 °C), a rise of 90 °F, but DOE warns that water at 140 °F raises the risk of scalding.

If you know the temperature of your incoming water, enter it instead: a colder supply means a larger rise. The temperature unit in the form converts the numbers you typed between °F and °C.

Worked example: a shower and a faucet

This is the DOE example. A shower head of 2.5 gallons per minute and a faucet of 0.75 gallons per minute run at the same time, with water coming in at 50 °F and heated to 120 °F.

  • Flow rate: 2.5 + 0.75 = 3.25 gpm, or 12.3 liters per minute
  • Temperature rise: 120 − 50 = 70 °F

So look for a model that gives at least 3.25 gpm at a 70 °F rise. With two showers running instead of one, the flow rate becomes 5.75 gpm. Heating to 140 °F for a dishwasher makes the rise 90 °F. Compare both numbers with the flow and rise chart in the maker's literature.

Sizing a storage water heater by first hour rating

For a tank, DOE uses the first hour rating: the number of gallons of hot water the heater can supply in an hour, starting with a full tank. It is on the EnergyGuide label or in the maker's literature. DOE advises a model whose first hour rating at least matches your peak hour demand, which is the hot water used in the busiest hour of the day.

Gallons of hot water per use, DOE peak hour worksheet
UseGallons per use
Shower20
Shaving (0.05 gallon per minute)2
Hand dishwashing or food prep (2 gallons per minute)3
Automatic dishwasher7
Clothes washer, top-loader25
Clothes washer, H-axis15

Count each use in that hour, multiply by the gallons per use, and add up the gallons. That total is your peak hour demand.

Worked example: a busy morning

In the DOE worksheet example, the busiest hour has 3 showers, 1 shave and 1 hand dishwashing: 3 × 20 + 1 × 2 + 1 × 3 = 65 gallons. The DOE page prints a total of 66 gallons for these rows, but the rows add up to 65. A tank with a first hour rating of at least 66 gallons, the total the DOE prints, covers that hour either way.

A family with 2 showers, a hand dishwashing, a dishwasher load and a top-loader load in the same hour needs 75 gallons. Moving the laundry to another hour drops it to 50 gallons, so a smaller first hour rating covers it. To estimate what an appliance costs to run, see the electricity cost calculator, and for the volume of a tank you already own, the tank volume calculator. Have a qualified installer confirm the choice against your local code before you buy.

Water Heater Size Calculator FAQ

What size tankless water heater do I need?

One that gives your flow rate at your temperature rise. For one 2.5 gpm shower and one 0.75 gpm faucet with 50 °F water heated to 120 °F, that is 3.25 gpm at a 70 °F rise.

What incoming water temperature should I use?

DOE says to assume 50 °F (10 °C) unless you know otherwise. If you have measured your cold water, use that number.

What is a first hour rating?

The gallons of hot water a storage water heater can supply in an hour, starting with a full tank. It is printed on the EnergyGuide label.

How many gallons does a shower use in the DOE worksheet?

The worksheet counts 20 gallons of hot water per shower, 25 per top-loader washer load and 7 per dishwasher load.

Does tank size equal the first hour rating?

No. DOE says the first hour rating depends on the tank capacity, the source of heat and the size of the burner or element, so compare the rating, not only the gallons of the tank.

Last updated . Free to use, no sign-up. How we check our numbers.