GuideElectrical & Energy

Voltage Drop Chart for Copper Wire

See how many volts 14 to 2 AWG copper loses over 25 to 200 feet, and what that is as a percent of 120 V or 240 V, so you can pick a wire size before you buy.

Updated 8 min read

Short answer

At 16 amps, 12 AWG copper loses 1.58 V over 25 ft one way, 3.17 V over 50 ft and 6.34 V over 100 ft. That is 5.28% of 120 V at 100 ft. The formula is 2 × length × amps × ohms per 1,000 ft ÷ 1,000. The NEC only recommends 3% for a branch circuit.

Do the math for your project

Voltage Drop Calculator

Volts lost along a copper or aluminum wire from its size, length and current, as a percent of the source.

Open the Voltage Drop Calculator

How many volts does copper wire lose over 25 to 200 feet?

At 16 amps, 12 AWG copper loses 1.58 V over 25 ft one way, 3.17 V over 50 ft, 6.34 V over 100 ft and 12.67 V over 200 ft. The loss grows in direct proportion to length, and thicker wire loses less. The same volts are lost on a 120 V or a 240 V circuit.

Every cell below assumes a single-phase circuit, copper wire, a 16 amp load (80% of a 20 amp breaker, which is also the default load of the voltage drop calculator) and the one-way distance from the source to the load. The resistance of each wire size is the one the voltage drop calculator uses: direct-current resistance at 75°C (167°F), as listed for copper in Michigan State University's Electrical Tech Note 212. Each cell was produced by running that calculator's own function, so the chart and the tool agree.

Volts lost, copper wire at 16 amps (any source voltage)
Wire size25 ft50 ft100 ft200 ft
14 AWG2.515.0210.0520.10
12 AWG1.583.176.3412.67
10 AWG0.991.983.977.94
8 AWG0.621.242.494.98
6 AWG0.390.791.573.14
4 AWG0.250.490.991.97
3 AWG0.200.390.781.57
2 AWG0.160.310.621.24

The chart shows voltage drop only and does not check whether a wire is rated for 16 amps. The ampacity of the wire, the breaker and the local code are separate checks that a licensed electrician makes. Reading the chart first avoids buying a wire that carries the current but loses too much voltage over a long run.

What percent of 120 V or 240 V is lost?

Divide the volts lost by the source voltage. The same wire, length and current lose half the percentage at 240 V that they lose at 120 V. A 100 ft run of 12 AWG at 16 amps loses 5.28% of 120 V but 2.64% of 240 V. Compare each cell with the 3% recommendation covered below.

Percent drop on a 120 V circuit, copper wire at 16 amps
Wire size25 ft50 ft100 ft200 ft
14 AWG2.09%4.19%8.37%16.75%
12 AWG1.32%2.64%5.28%10.56%
10 AWG0.83%1.65%3.31%6.61%
8 AWG0.52%1.04%2.07%4.15%
6 AWG0.33%0.65%1.31%2.62%
4 AWG0.21%0.41%0.82%1.64%
3 AWG0.16%0.33%0.65%1.31%
2 AWG0.13%0.26%0.52%1.03%
Percent drop on a 240 V circuit, copper wire at 16 amps
Wire size25 ft50 ft100 ft200 ft
14 AWG1.05%2.09%4.19%8.37%
12 AWG0.66%1.32%2.64%5.28%
10 AWG0.41%0.83%1.65%3.31%
8 AWG0.26%0.52%1.04%2.07%
6 AWG0.16%0.33%0.65%1.31%
4 AWG0.10%0.21%0.41%0.82%
3 AWG0.08%0.16%0.33%0.65%
2 AWG0.06%0.13%0.26%0.52%

The 240 V table is the 120 V table divided by 2, because the volts lost are identical and only the source voltage changes. If a load can use either voltage, the higher one avoids a bigger wire on a long run. The load must be rated for the voltage you choose.

Open this example in the voltage drop calculator

What is the voltage drop formula for a wire run?

For a single-phase or direct-current circuit, the voltage drop is 2 × one-way length in feet × current in amps × the wire's resistance in ohms per 1,000 ft ÷ 1,000. The factor 2 counts the current going out to the load and coming back on the other conductor. A three-phase circuit uses 1.732 instead of 2.

Voltage drop = 2 × length × amps × ohms per 1,000 ft ÷ 1,000
Percent drop = voltage drop ÷ source voltage × 100

Example: a 120 V circuit carries 16 amps over 100 ft of 12 AWG copper. The table of conductor resistance in Michigan State's Electrical Tech Note 212 gives 1.98 ohms per 1,000 ft for this size.

  • Resistance of the run: 2 × 100 × 1.98 ÷ 1,000 = 0.396 ohms
  • Voltage drop: 0.396 × 16 = 6.336 V, shown as 6.34 V in the chart
  • Percent drop: 6.336 ÷ 120 × 100 = 5.28%
  • Voltage at the load: 120 − 6.336 = 113.66 V

Moving to 10 AWG gives 3.31% and 8 AWG gives 2.07%, so 8 AWG is the first size in the chart under 3% for this run at 120 V. The same 12 AWG run on a 240 V source loses 2.64%. If you have watts instead of amps, the watts to amps calculator converts them, and the guide to watts, amps and volts explains why.

How far can I run each wire size within 3% or 5%?

Turn the formula around to get the longest run for a drop limit. At 16 amps on 120 V, 12 AWG copper stays within 3% up to 56 ft one way and within 5% up to 94 ft. At 240 V those distances are about twice as long. The table lists whole feet for each size.

Longest one-way run in feet, copper wire at 16 amps
Wire size3% at 120 V5% at 120 V3% at 240 V5% at 240 V
14 AWG355971119
12 AWG5694113189
10 AWG90151181302
8 AWG144241289482
6 AWG229381458763
4 AWG3656087301,217
3 AWG4597659181,530
2 AWG5799661,1591,932

Reading it: a 150 ft run at 120 V and 16 amps needs a size whose 3% length is at least 150 ft, and the table shows 6 AWG as the first size that qualifies. The same run at 240 V qualifies with 10 AWG. A shorter run, a thicker wire or a higher voltage each avoid the problem, and the choice depends on the load and the cost of the wire.

These distances apply only to 16 amps. For another current, scale them: a 20 amp load gets 16 ÷ 20 = 0.8 of each distance. For an exact answer, enter your own numbers in the voltage drop calculator.

Does the NEC set a maximum voltage drop?

For branch circuits, the NEC gives a recommendation, not a requirement. EC&M (2015) reports 3% for any branch circuit and 5% for the feeder and branch circuit combined, both in informational notes, and says these are not NEC requirements. The note after 210.19(A) covers the branch circuit.

The note's number depends on the edition. EC&M (2015) places it in Informational Note No. 4 following 210.19(A). That numbering was not confirmed in the NFPA 70 text. NECA's 2023 summary says Section 210.19 now applies to branch circuits up to 1,000 V ac and 1,500 V dc, and no page that this guide read shows where the note sits in that edition. Check the edition your jurisdiction has adopted.

The technical page of Allied Wire & Cable puts it the same way: the NEC recommends that the branch circuit stay at or below 3%, and this is only a recommendation and not mandatory. EC&M adds that sensitive electronic equipment under Article 647 has a mandatory limit at half the recommended values.

Check locally: a local code, an inspector, a utility or an equipment maker can set a stricter limit than these recommendations. Cerrowire's own 3% tables for 25 to 200 ft call themselves only a guide and send readers to an engineer. A licensed electrician decides for your job.

How do I adjust the chart for other amps or aluminum wire?

Volts lost are proportional to current, so multiply any table value by your amps ÷ 16. A 20 amp load on 100 ft of 12 AWG copper loses 6.34 × 20 ÷ 16 = 7.92 V, which matches the calculator. An 8 amp load loses half of the table value. The percent scales the same way.

Aluminum has more resistance than copper. For 12 AWG the calculator uses 3.25 ohms per 1,000 ft for aluminum, the value in Michigan State's Electrical Tech Note 212, against 1.98 for copper, so 100 ft at 16 amps loses 10.40 V, which is 1.64 times the copper figure. Aluminum needs its own run of the calculator, or a larger size.

What the chart leaves out: the wire's temperature, conduit and how it is installed, and on alternating current the reactance of large conductors and the power factor of the load. Those can make the real drop higher than the figure shown. The values are planning estimates. For a load in watts, convert it to amps first, then read the chart. The generator size calculator and the solar panel calculator size the source that feeds the wire.

Frequently asked questions

What is the voltage drop of 12 gauge wire over 100 feet?

At 16 amps, 12 AWG copper loses 6.34 V over 100 feet one way, which is 5.28% of 120 V and 2.64% of 240 V. At 20 amps it loses 7.92 V.

How do I read a voltage drop chart?

Find your wire size in the row, your one-way length in the column and read the volts lost for the current the chart states. Scale it to your amps, then divide by the source voltage to get the percent.

Is a 5% voltage drop acceptable?

The NEC recommends 3% for a branch circuit and 5% for feeder and branch circuit combined, according to EC&M. Both are recommendations, not requirements. Local code and equipment ratings can be stricter.

Does 240 volts reduce voltage drop?

It lowers the percent. The same wire, length and current lose the same volts, but that is half the share of a 240 V source: 5.28% at 120 V against 2.64% at 240 V for 12 AWG over 100 feet.

Why is the length multiplied by 2 in the voltage drop formula?

On a single-phase or direct-current circuit the current travels to the load on one conductor and returns on the other, so the resistance of twice the one-way length counts.

Sources

  1. EC&M: Watch Out for that Voltage Drop (2015)ecmweb.com
  2. Michigan State University, Biosystems & Agricultural Engineering: Electrical Tech Note 212, Table 212.1 (conductor resistance)maec.msu.edu
  3. IAEI Magazine: Voltage Drop Formulasiaeimagazine.org
  4. Allied Wire & Cable: Voltage Dropawcwire.com
  5. Cerrowire: Voltage Drop Tablescerrowire.com
  6. NECA 2023 convention: Top 20 changes in the 2023 NEC (Mark Earley)necaconvention.org

Last updated . Free to read, no sign-up. How we check our numbers.