Why there is no honest size per square foot
None of the federal sources read for this guide publishes a table that turns square footage into Btu, and the U.S. Department of Energy (DOE) explains the problem with rules of thumb. In the past, many HVAC contractors used rules of thumb to size equipment, and as a result many installed oversized systems. The DOE says many older furnaces and central air conditioners are oversized.
| Source | What it says |
|---|---|
| ENERGY STAR | Bigger is not always better. Ask the contractor to verify the proper size with a Manual J calculation |
| U.S. Department of Energy (Building America) | Contractors who used rules of thumb often installed oversized systems. A trained contractor should determine the loads with the ACCA calculations |
| DOE Strategy Guideline: HVAC Equipment Sizing | Manual S recommends a furnace size within 140% of the peak heating load estimate |
| ACCA | Manual J is the national ANSI-recognized standard for producing HVAC equipment sizing loads |
Two houses with the same floor area can need very different furnaces. One may have thin attic insulation, leaky ducts and a cold climate; the other tight walls and a mild climate. Square footage tells you the size of the floor, not how fast the building loses heat. That is why the sources send you to a calculation instead of a number.
The BTU calculator on this site is built for room air conditioners and uses the ENERGY STAR sizing chart. It does not size a furnace, and neither does the square footage calculator, which only gives you the floor area to hand to a contractor.
What a Manual J load calculation uses
The Air Conditioning Contractors of America (ACCA) publishes Manual J. The ACCA page calls the 8th edition the national ANSI-recognized standard for producing HVAC equipment sizing loads, for single-family detached homes, small multi-unit structures, condominiums, townhouses and manufactured homes. It adds that a proper load calculation following the procedure is required by national building codes and most state and local jurisdictions.
The DOE Strategy Guideline and a heat pump sizing guide hosted on a DOE site describe what goes in:
- The building shell. The surface areas and thermal properties of the building enclosure.
- Air leakage. The air leakage in the building. The heat pump guide says infiltration estimates are often overstated and recommends blower door testing.
- Duct losses. Counted only when the ducts will be used by the new equipment.
- Design temperatures. The indoor and outdoor conditions for the location. The DOE Strategy Guideline's examples use 70°F indoors for heating and an outdoor design temperature set by place, such as 38°F for its Orlando house, and it notes that elevation matters too.
The heat pump guide also says that load calculations have safety factors built in. This is why a number from a rule of thumb, which hides all of these inputs, is a weak starting point.
Reading your furnace: input, output and AFUE
Furnace efficiency is rated in AFUE, annual fuel utilization efficiency. The DOE defines it as the ratio of heat output of the furnace to the total amount of fuel consumed, and gives an example: an AFUE of 90% means that 90% of the energy in the fuel becomes heat for the home. The same guide puts mid-efficiency furnaces at 80% to 82% and sealed-combustion condensing furnaces at 90% to 98%.
So the heat a furnace delivers is roughly its fuel input times its AFUE. AFUE is an annual figure, so this is an estimate. If the furnace label lists an output capacity, use that figure instead.
Output (Btu per hour) ≈ input (Btu per hour) × AFUE ÷ 100
| Input rating (Btu per hour) | Output at 80% AFUE | Output at 90% AFUE | Output at 96% AFUE |
|---|---|---|---|
| 60,000 | 48,000 | 54,000 | 57,600 |
| 80,000 | 64,000 | 72,000 | 76,800 |
| 100,000 | 80,000 | 90,000 | 96,000 |
The 96% column is an example inside the DOE's 90% to 98% range for condensing furnaces, not a rating of any one model. The table shows why two furnaces with the same input can deliver different heat.
What a furnace that is too big does
ENERGY STAR says bigger is not always better. A conventional system that is too large may not keep your home comfortable because of frequent on/off cycling, and oversized units tend to have shorter lives due to short cycling, which causes wear on the compressor (a part of air conditioners and heat pumps). It adds that higher efficiency equipment with variable speed compressors does a better job of compensating for any oversizing. A guide hosted on a DOE site says grossly oversizing equipment can lead to excessive cycling and low efficiency.
The DOE Strategy Guideline for HVAC equipment sizing, by Arlan Burdick of IBACOS (February 2012), adds a warning for homes that have central air conditioning: selecting equipment based on the cooling load may lead to a furnace that is oversized for the heating load. It also quotes the Manual S limit: furnace size within 140% of the peak heating load estimate.
| Peak heating load (Btu per hour, made-up example) | 140% of the load |
|---|---|
| 30,000 | 42,000 |
| 40,000 | 56,000 |
| 50,000 | 70,000 |
| 60,000 | 84,000 |
Here is how that works with a made-up Manual J peak heating load of 40,000 Btu per hour. The limit is 56,000 Btu per hour. The guideline does not say whether its limit means input or output, so this example compares output capacity, because the load is heat the house needs.
- An old furnace with 100,000 Btu per hour of input at 80% AFUE delivers about 80,000 Btu per hour, which is 200% of the load.
- A furnace with 60,000 Btu per hour of input at 96% AFUE delivers about 57,600 Btu per hour, which is 144% of the load.
- A furnace with 50,000 Btu per hour of input at 96% AFUE delivers about 48,000 Btu per hour, which is 120% of the load.
The DOE adds that a newer furnace may be more efficient but is still likely to be oversized.
If you are choosing a heat pump instead
Heat pumps follow different sizing rules in cold climates. The DOE Building America guide says that in a cold climate the contractor may opt for a larger heat pump than Manual S indicates, to reduce the need for backup heat, and that this is a tradeoff because the heat pump may then be oversized for the cooling load. It also says furnaces deliver air at 130°F to 140°F while heat pumps deliver air at about 80°F to 115°F, so more air has to be delivered for the same warmth, and ducts may need to be larger for a heat pump than for a gas or oil furnace.
A guide to sizing air-source heat pumps in cold climates, hosted on a DOE site, says that for a full replacement or a new system, capacity at the design temperature should match 100% to 115% of the estimated heating load. Rules differ by equipment, and ENERGY STAR's advice stands for heat pumps too: have the contractor verify the size with Manual J.
Insulate and seal first, then size
The DOE says that with a better building envelope the new furnace or boiler can sometimes be a smaller size than the original, and that an energy performance contractor can run analysis software to determine your heating and cooling needs after air sealing and insulation improvements are made. The order the DOE describes is improvements first, then the load analysis.
The insulation calculator shows how many bags or batts an attic needs for a target R-value, and the guide R-value chart shows what the numbers mean.
What to ask a contractor
- Do you verify the size with Manual J? ENERGY STAR tells homeowners to make sure the contractor verifies the proper size system for the home with Manual J.
- Will you inspect the house? ENERGY STAR lists an on-site inspection and a detailed bid among the signs of a good contractor, and credentials such as NATE or ACCA installation certification.
- How do my upgrades change the size? The DOE says to talk to the contractor about how energy improvements will affect your furnace system.
- Are my ducts sized for it? For a heat pump, the DOE says to ask the HVAC installer to confirm that the existing ducts are appropriately sized.
The answers decide the size. The local code and your contractor's load calculation have the last word.
Estimating what the furnace will cost to run
Once the size is settled, compare fuels by the heat they deliver, not by the price on the delivery ticket. The cost per million Btu of useful heat is the price per unit of fuel divided by the Btu in that unit times the AFUE, then multiplied by 1,000,000.
Cost per million Btu of heat = price per unit ÷ (Btu per unit × AFUE ÷ 100) × 1,000,000
The heating cost calculator does this arithmetic for gas, oil, propane, wood and electricity with your own prices and furnace efficiency. For the units behind it, read what is a BTU.
Frequently asked questions
How many BTUs do I need to heat 1,000 square feet?
The DOE and ENERGY STAR pages read for this guide give no Btu-per-square-foot figure. They say to size heating equipment with a Manual J load calculation, which uses the building shell, air leakage, duct losses and the design temperatures for your location.
What is a Manual J load calculation?
It is the ACCA procedure for estimating the heat loss and heat gain of a home, described by the ACCA as the national ANSI-recognized standard for producing HVAC equipment sizing loads. The DOE says Manual S then guides equipment selection and Manual D covers ducts.
Is a bigger furnace better?
No. ENERGY STAR says bigger is not always better: a system that is too large may not keep your home comfortable because of frequent on/off cycling, and oversized units tend to have shorter lives.
Can my new furnace be smaller than my old one?
Sometimes. The DOE says that with a better building envelope the new furnace or boiler can sometimes be a smaller size than the original. Older furnaces are often oversized to begin with.
How much bigger than the heating load can a furnace be?
The DOE Strategy Guideline for HVAC equipment sizing says Manual S recommends a furnace size within 140% of the peak heating load estimate. For a load of 40,000 Btu per hour that is 56,000 Btu per hour.
Sources
- ENERGY STAR: Clean Heating and Coolingenergystar.gov
- U.S. DOE Building America: Energy Renovations, HVAC, A Guide for Contractors to Share with Homeownersenergy.gov
- U.S. DOE Building America: Strategy Guideline, HVAC Equipment Sizing (Burdick, IBACOS, February 2012)www1.eere.energy.gov
- ACCA: Manual J, Residential Load Calculationacca.org
- Guide to Sizing and Selecting Air-Source Heat Pumps in Cold Climates (rev. 04/08/20, hosted by DOE)bsesc.energy.gov