How many kWh does a heat pump use?
A heat pump moves heat instead of making it, so its electricity use depends on two numbers: the heat your home needs and the heat pump's efficiency. Efficiency is rated as HSPF2, the heating seasonal performance factor. ENERGY STAR's open data defines it as the total heating output over the heating period divided by the total electrical input, in Btu per watt-hour.
kWh = Btu of heat ÷ (HSPF2 × 1,000)
COP = HSPF2 ÷ 3.412
The second line comes from the EIA conversion of 1 kilowatthour = 3,412 Btu. A watt-hour is 3.412 Btu, so an HSPF2 of 8.5 means 8.5 ÷ 3.412 = 2.49 units of heat for each unit of electricity. That ratio is the coefficient of performance (COP). The DOE says an air-source heat pump can deliver up to three times more heat energy than the electrical energy it consumes. A COP of 3 matches an HSPF2 of 10.2.
| Efficiency | COP | kWh per million Btu of heat | Watts for 12,000 Btu per hour | Cost per million Btu |
|---|---|---|---|---|
| Electric resistance (1 kWh gives 3,412 Btu) | 1.00 | 293.1 | 3,517 | $53.25 |
| HSPF2 7.5 | 2.20 | 133.3 | 1,600 | $24.23 |
| HSPF2 8.5 | 2.49 | 117.6 | 1,412 | $21.38 |
| HSPF2 9.0 | 2.64 | 111.1 | 1,333 | $20.19 |
| HSPF2 10.0 | 2.93 | 100.0 | 1,200 | $18.17 |
| HSPF2 12.0 | 3.52 | 83.3 | 1,000 | $15.14 |
The cost column is the result of the heating cost calculator for the same COP and price. See the guide on what a Btu is for the units, and the guide on the kilowatt-hour for the electricity side.
How many watts does a heat pump use?
Watts depend on how much heat the unit is delivering at that moment. For a given output in Btu per hour, divide by the efficiency in Btu per watt-hour.
Watts = Btu per hour of heat ÷ HSPF2
| Heat output in Btu per hour | Electric resistance | HSPF2 8.5 | HSPF2 10 |
|---|---|---|---|
| 12,000 | 3,517 W | 1,412 W | 1,200 W |
| 24,000 | 7,034 W | 2,824 W | 2,400 W |
| 33,600 (median of listed models) | 9,848 W | 3,953 W | 3,360 W |
| 36,000 | 10,551 W | 4,235 W | 3,600 W |
| 48,000 | 14,068 W | 5,647 W | 4,800 W |
| 60,000 | 17,585 W | 7,059 W | 6,000 W |
This is the average input if the unit ran at that output with the seasonal efficiency of the rating. The rating is an average over a standard heating season, so a real unit's draw at any moment differs. The table shows the scale of the draw, not a reading from a meter. The middle row is the median heating capacity at 47 °F among the 283,108 listed combinations.
The watts also set the circuit. Use the watts to amps calculator to turn a nameplate wattage into amps. A portable electric heater is a different case, covered in the guide on watts used by a space heater.
What HSPF2 do ENERGY STAR heat pumps actually have?
We downloaded the ENERGY STAR list of certified air-source heat pumps (updated November 12, 2026) and kept the 283,108 combinations sold in the United States. Each row is one certified pairing of outdoor and indoor units, so the counts show how many pairings exist, not how many were sold.
| Type | Listed combinations | Lowest HSPF2 | Median HSPF2 | Highest HSPF2 |
|---|---|---|---|---|
| Split system | 265,097 | 7.5 | 8.5 | 11.0 |
| Mini or multi split | 17,177 | 7.7 | 10.0 | 17.5 |
| Single package | 834 | 7.2 | 8.55 | 9.85 |
| All types | 283,108 | 7.2 | 8.5 | 17.5 |
The median combination rates HSPF2 8.5, a COP of 2.49. Mini and multi splits sit higher, at a median of 10.0, or a COP of 2.93. The bands show how the listings spread.
| HSPF2 band | Share of listings | COP range |
|---|---|---|
| Under 8 | 16.0% | below 2.34 |
| 8 to under 9 | 53.4% | 2.34 to under 2.64 |
| 9 to under 10 | 25.1% | 2.64 to under 2.93 |
| 10 to under 11 | 4.2% | 2.93 to under 3.22 |
| 11 or more | 1.3% | 3.22 or more |
More than half of the combinations fall between 8 and 9. Only 5.5% reach 10 or more. Since kWh falls in proportion to HSPF2, a combination at 10 uses 15% less electricity than one at 8.5 for the same heat.
The rating describes a standard heating season. Your own winter may be colder or milder than the one behind the number, so use the table as a guide to the ranking of models, not as a bill forecast.
What does a heat pump cost to run per month in winter?
Start with the heat your home needs in the month, in million Btu, and divide by the efficiency. The table prices that heat at 18.17 cents per kWh, the EIA residential average for September 2026 from the Electricity Monthly Update released on November 24, 2026. Your bill shows your own rate.
| Heat the home needs in the month | Electric resistance | HSPF2 8.5 | HSPF2 10 |
|---|---|---|---|
| 5 million Btu | 1,465 kWh, $266 | 588 kWh, $107 | 500 kWh, $91 |
| 10 million Btu | 2,931 kWh, $533 | 1,176 kWh, $214 | 1,000 kWh, $182 |
| 15 million Btu | 4,396 kWh, $799 | 1,765 kWh, $321 | 1,500 kWh, $273 |
| 20 million Btu | 5,862 kWh, $1,065 | 2,353 kWh, $428 | 2,000 kWh, $363 |
| 30 million Btu | 8,792 kWh, $1,598 | 3,529 kWh, $641 | 3,000 kWh, $545 |
The heat figures are examples. No national figure for a month of heat is used here, because it depends on the climate, the house and the winter. Your own past bills give the best number. If your gas bill is in therms, EIA gives 1 therm = 100,000 Btu. A month of 80 therms through an 80% efficient furnace delivered 80 × 100,000 × 0.8 = 6.4 million Btu of heat. At HSPF2 8.5 that heat takes 753 kWh, or $136.81.
Worked example: 10 million Btu in a month, COP 2.5
A COP of 2.5 is an HSPF2 of 2.5 × 3.412 = 8.53.
- Electricity: 10,000,000 ÷ (3,412 × 2.5) = 1,172.3 kWh.
- Cost: 1,172.3 × 18.17 ÷ 100 = $213.01, or $21.30 per million Btu.
- For comparison, the same heat from resistance elements takes 2,931 kWh and costs $532.53.
The heating cost calculator returns $213.01 for the heat pump row with these inputs. It also lists natural gas, oil and propane at its default prices. Enter your own prices there, and use the electricity cost calculator for any single device.
Why does a heat pump use more electricity on the coldest days?
A heat pump delivers less heat as the outdoor air gets colder, while the house needs more. ENERGY STAR cold climate certification requires third-party verified low-temperature performance, with testing down to 5 °F. ENERGY STAR adds that cold climate units can keep running below 5 °F, and that pairing a heat pump with a backup heat source is most efficient at lower temperatures.
The certified list shows the capacity at 47 °F, 17 °F and 5 °F for each combination. We took each combination's capacity at the colder temperature as a percentage of its 47 °F capacity, and the table gives the median. Of the 283,108 listed combinations, 146,984 are flagged as cold climate.
| Outdoor temperature | Cold climate listings | Other listings |
|---|---|---|
| 47 °F | 100% | 100% |
| 17 °F | 82.8% | 64.7% |
| 5 °F | 78.2% | 51.7% |
A typical cold climate model keeps about 78% of its capacity at 5 °F, against about 52% for the others. When the capacity falls short of what the house needs, a backup heat source supplies the rest. If that backup is electric resistance, the missing heat costs 3,412 Btu per kWh, the COP 1 row of the first table. So electricity use per unit of heat rises in a cold spell, and the seasonal rating does not show it.
Insulation and air sealing cut the heat the house needs, which cuts the kWh in every table above. The insulation calculator and the BTU calculator are the next steps.
How much electricity do homes use for electric heating?
EIA's 2020 Residential Energy Consumption Survey (RECS) reports 2,484 kWh a year for space heating in homes that use electricity for it. The table's footnote says the figure includes main and secondary space heating, and the table does not split it by equipment, so it cannot be read as a heat pump average. At 18.17 cents it comes to $451.34 a year. EIA lists it at 2,876 kWh for homes in very cold and cold climates, 3,109 in the Midwest, 2,603 in the South and 1,840 in the West.
For a comparison with resistance heat, the DOE cites a study by the Northeast Energy Efficiency Partnerships of units designed for colder regions installed in the Northeast and Mid-Atlantic. It reports annual savings of around 3,000 kWh, or $459, compared with electric resistance heaters. That is one study of cold climate units in two regions, so your own saving depends on your climate, house and prices.
This guide covers heating only. Size is a separate question. ENERGY STAR says a contractor should use a Manual J calculation to size the system, and the guide on furnace size explains why square footage alone does not decide it.
Frequently asked questions
How many kWh does a heat pump use in a winter month?
It depends on the heat your home needs. At HSPF2 8.5, each 10 million Btu of heat takes 1,176 kWh, which costs $213.76 at 18.17 cents per kWh.
How many watts does a heat pump delivering 36,000 Btu per hour use?
At HSPF2 8.5, 36,000 Btu per hour of heat takes about 4,235 W, and at HSPF2 10 about 3,600 W, while running at that output.
How do I convert HSPF2 to COP?
Divide HSPF2 by 3.412, because 1 kWh equals 3,412 Btu. HSPF2 8.5 is a COP of 2.49, and HSPF2 10 is 2.93.
Do heat pumps still heat at 5 degrees F?
ENERGY STAR cold climate models are tested down to 5 °F. In the certified list, their median capacity at 5 °F is 78.2% of the capacity at 47 °F, against 51.7% for the other models.
What size heat pump do I need for a 2,000 square foot house?
Square footage alone does not decide it. ENERGY STAR says a contractor should size the system with a Manual J load calculation of the home.
Sources
- EIA: Units and calculators explained, British thermal units (Btu)eia.gov
- EIA: Electricity Monthly Update, end-use prices (September 2026)eia.gov
- EIA: 2020 RECS, Table CE5.3a (kWh version), Detailed household site electricity end-use consumption, part 1, averages, kWh per household using the end useeia.gov
- ENERGY STAR: ENERGY STAR Certified Air-Source Heat Pumps (open data set)data.energystar.gov
- ENERGY STAR: Air-Source Heat Pumpsenergystar.gov
- US DOE: Air-Source Heat Pumpsenergy.gov